Protocol
-
BACnet®
- B/IP x 2, Ethernet, MS/TP, and PTP
- RCP -
Reliable Controls®
Protocol (RCP) for backward compatibility with previous generation systems
- Modbus - Support both RTU and TCP in both master and slave configurations
return to top
|
12 Inputs
- Universal ranges
- 12 universal inputs
- Expandable to 96 inputs using MACH-ProPointTM expansion modules
- 12-bit ADC
- Analog: 0-5 VDC, 0-10 VDC, 4-20 mA, thermistor
- Digital: dry contact
- Impedance:
15k O on 0-5 VDC range
15k O on 0-10 VDC range
250 O on 4-20 mA range
- 150 Hz pulse counting (supports flow meters)
- 24 VAC over voltage protection
|
8 Outputs
- Universal ranges
- 4 outputs support either relay or universal modules
- 8 universal outputs
- Expandable to 64 outputs using MACH-ProPointTM expansion modules
- 12-bit DAC
- First four outputs are socketted to accommodate relay module or universal module (output modules sold separately)
- Analog: 0-12 VDC
- Digital: 0-12 VDC
- Manual ON provides adjustable 0-12 VDC (HOA only)
- LED indicator (glows proportionally)
- Output power: 75 mA @ 12 VDC
- 24 VAC over voltage and short protection
return to top
|
256 Variables
- Selectable standard and custom ranges, as well as fixed program-driven values
|
64 PID Controllers
- Standard P, PI, or PID controllers for closed loop control
-
BACnet®
loops supported
return to top
|
32 Weekly Schedules
- 4 on/off times for each weekday and 2 override days
-
BACnet®
schedules supported
|
8 Annual Schedules
- Days of the year designated as holidays
-
BACnet®
calendar supported
return to top
|
20 Custom Tables
- For creating custom input ranges
|
64 System Groups
- Allows related points to be grouped on to one display
- 160 points / group
return to top
|
128 Control-BASICTM Programs
- User programmable control strategy in a readable, BASIC-like language
- 2500 bytes per program
|
96 Trend Logs
- Each trend log stores 512 samples and up to 6 points
- Values recorded at user defined intervals
-
BACnet®
trend logs supported
return to top
|
128 Runtime Logs
- Totals the on time and records the on/off times of a digital point
- Holds 200 events
|
128 User Passwords
- Protects access to system
- Each user is assigned a user name and an access level
return to top
|
16 Custom Units
- 8 analog engineering units
- 8 digital engineering units
|
SMART-NetTM Port
- Networks up to 16 SMART-SensorsTM
return to top
|
Real-Time Clock
|
Warranty
return to top
|
Processor
- 100 mHz, high-performance
- 32-bit embedded microcontroller
return to top
|
Memory
- 8MB operating RAM
- 1MB non-volitile RAM (trends and dynamic values)
- 2 MB Flash EEPROM operating system, database, and controller configuration
|
Supply Voltages
return to top
|
Communications
- IEEE 802.3 Ethernet 10/100 BaseT
- 2 EIA-485 @ 76.8 kbps max.
- 1 EIA-232 @ 115.2 kbps max. PC or modem
- SMART-NetTM Port
|
Peripheral Power
- Onboard variable 15-24 VDC power supply providing up to 200 mA of DC power to peripheral devices
return to top
|
Memory/RTC Backup
- 72 hour battery backup
- 10 years for database 1 year lithium (offline)
|
I/O Expansion Modules
- Up to 7 ProPointTM expansion modules with 12 universal inputs and 8 outputs each
- 12 universal inputs
- 12-bit ADC inputs
- 12-bit DAC outputs
- Output modules (relay or universal) sold separately
return to top
|
Dimensions
- 25.4 cm L x 13.7 cm W x 3.84 cm H
- (10" L x 5.39" W x 1.51" H)
|
Mounting
- #8 clearance holes on 23.0 cm L x 11 cm W (9.06" L x 4.33" W
return to top
|
Weight
|
Ambient Limits
- Operating: 0 ºC to 40 ºC (32 ºF to 104 ºF)
- Shipping: -40 ºC to 60 ºC (-40 ºF to 140 ºF)
- Humidity: 10% to 90% RH non-condensing
return to top
|