MACH-ProSys BACnet Building Controller

MACH-ProSys

Ideal for large installation projects, the Reliable Controls® MACH-ProSys is a fully programmable, high-performance BACnet building controller.

Features:

Protocol

  • BACnet® - B/IP x 2, Ethernet, MS/TP, and PTP
  • RCP - Reliable Controls® Protocol (RCP) for backward compatibility with previous generation systems
  • Modbus - Support both RTU and TCP in both master and slave configurations

return to top

12 Inputs

  • Universal ranges
  • 12 universal inputs
  • Expandable to 96 inputs using MACH-ProPointTM expansion modules
  • 12-bit ADC
  • Analog: 0-5 VDC, 0-10 VDC, 4-20 mA, thermistor
  • Digital: dry contact
  • Impedance:
    15k O on 0-5 VDC range
    15k O on 0-10 VDC range
    250 O on 4-20 mA range
  • 150 Hz pulse counting (supports flow meters)
  • 24 VAC over voltage protection


8 Outputs

  • Universal ranges
  • 4 outputs support either relay or universal modules
  • 8 universal outputs
  • Expandable to 64 outputs using MACH-ProPointTM expansion modules
  • 12-bit DAC
  • First four outputs are socketted to accommodate relay module or universal module (output modules sold separately)
  • Analog: 0-12 VDC
  • Digital: 0-12 VDC
  • Manual ON provides adjustable 0-12 VDC (HOA only)
  • LED indicator (glows proportionally)
  • Output power: 75 mA @ 12 VDC
  • 24 VAC over voltage and short protection

return to top


256 Variables

  • Selectable standard and custom ranges, as well as fixed program-driven values


64 PID Controllers

  • Standard P, PI, or PID controllers for closed loop control
  • BACnet® loops supported

return to top


32 Weekly Schedules

  • 4 on/off times for each weekday and 2 override days
  • BACnet® schedules supported


8 Annual Schedules

  • Days of the year designated as holidays
  • BACnet® calendar supported

return to top


20 Custom Tables

  • For creating custom input ranges


64 System Groups

  • Allows related points to be grouped on to one display
  • 160 points / group

return to top


128 Control-BASICTM Programs

  • User programmable control strategy in a readable, BASIC-like language
  • 2500 bytes per program


96 Trend Logs

  • Each trend log stores 512 samples and up to 6 points
  • Values recorded at user defined intervals
  • BACnet® trend logs supported

return to top


128 Runtime Logs

  • Totals the on time and records the on/off times of a digital point
  • Holds 200 events


128 User Passwords

  • Protects access to system
  • Each user is assigned a user name and an access level

return to top


16 Custom Units

  • 8 analog engineering units
  • 8 digital engineering units


SMART-NetTM Port

  • Networks up to 16 SMART-SensorsTM

return to top


Real-Time Clock

  • ±1 second per day


Warranty

  • Industry Best 5 years

return to top


Processor

  • 100 mHz, high-performance
  • 32-bit embedded microcontroller

return to top


Memory

  • 8MB operating RAM
  • 1MB non-volitile RAM (trends and dynamic values)
  • 2 MB Flash EEPROM operating system, database, and controller configuration


Supply Voltages

  • 24 VAC/VDC, 75 VA

return to top


Communications

  • IEEE 802.3 Ethernet 10/100 BaseT
  • 2 EIA-485 @ 76.8 kbps max.
  • 1 EIA-232 @ 115.2 kbps max. PC or modem
  • SMART-NetTM Port


Peripheral Power

  • Onboard variable 15-24 VDC power supply providing up to 200 mA of DC power to peripheral devices

return to top


Memory/RTC Backup

  • 72 hour battery backup
  • 10 years for database 1 year lithium (offline)


I/O Expansion Modules

  • Up to 7 ProPointTM expansion modules with 12 universal inputs and 8 outputs each
  • 12 universal inputs
  • 12-bit ADC inputs
  • 12-bit DAC outputs
  • Output modules (relay or universal) sold separately

return to top


Dimensions

  • 25.4 cm L x 13.7 cm W x 3.84 cm H
  • (10" L x 5.39" W x 1.51" H)


Mounting

  • #8 clearance holes on 23.0 cm L x 11 cm W (9.06" L x 4.33" W

return to top


Weight

  • 1.3 kg (2.7 lb.)


Ambient Limits

  • Operating: 0 ºC to 40 ºC (32 ºF to 104 ºF)
  • Shipping: -40 ºC to 60 ºC (-40 ºF to 140 ºF)
  • Humidity: 10% to 90% RH non-condensing

return to top



©2008 Control Network Services